Table 310.15(B)(1) — Ambient Temperature Correction Factors

formerly Table 310.15(B)(2)(a)

Ambient Temperature Correction Factors Based on 30°C (86°F)

For ambient temperatures other than 30°C (86°F), multiply the allowable ampacities specified in the ampacity tables by the appropriate correction factor shown below.

Ambient
Temperature (°C)
Temperature Rating of Conductor Ambient
Temperature (°F)
60°C 75°C 90°C
10 or less1.291.201.1550 or less
11-151.221.151.1251-59
16-201.151.111.0860-68
21-251.081.051.0469-77
26-301.001.001.0078-86
31-350.910.940.9687-95
36-400.820.880.9196-104
41-450.710.820.87105-113
46-500.580.750.82114-122
51-550.410.670.76123-131
56-600.580.71132-140
61-650.470.65141-149
66-700.330.58150-158
71-750.50159-167
76-800.41168-176
81-850.29177-185

Don't want to do ambient temperature correction by hand? The Conduit Size Calculator can take care of that for you!