Single-Phase Dwelling Services and Feeders
Service or Feeder Rating (amps) |
Conductor size (AWG or kcmil) | |
---|---|---|
Copper | Aluminum or copper-clad aluminum | |
100 | 4 | 2 |
110 | 3 | 1 |
125 | 2 | 1/0 |
150 | 1 | 2/0 |
175 | 1/0 | 3/0 |
200 | 2/0 | 4/0 |
225 | 3/0 | 250 |
250 | 4/0 | 300 |
300 | 250 | 350 |
350 | 350 | 500 |
400 | 400 | 600 |