Minimum Size Equipment Grounding Conductors for Grounding Raceway and Equipment
Max. circuit breaker size |
Conductor size (AWG or kcmil) | |
---|---|---|
Copper | Aluminum or copper-clad aluminum | |
15 | #14 | #12 |
20 | #12 | #10 |
60 | #10 | #8 |
100 | #8 | #6 |
200 | #6 | #4 |
300 | #4 | #2 |
400 | #3 | #1 |
500 | #2 | #1/0 |
600 | #1 | #2/0 |
800 | #1/0 | #3/0 |
1000 | #2/0 | #4/0 |
1200 | #3/0 | 250 |
1600 | #4/0 | 350 |
2000 | 250 | 400 |
2500 | 350 | 600 |
3000 | 400 | 600 |
4000 | 500 | 750 |
5000 | 700 | 1250 |
6000 | 800 | 1250 |