Table 250.122 — Grounding Conductor Size

Minimum Size Equipment Grounding Conductors for Grounding Raceway and Equipment

Max. circuit
breaker size
Conductor size (AWG or kcmil)
Copper Aluminum or copper-clad aluminum
15#14#12
20#12#10
60#10#8
100#8#6
200#6#4
300#4#2
400#3#1
500#2#1/0
600#1#2/0
800#1/0#3/0
1000#2/0#4/0
1200#3/0250
1600#4/0350
2000250400
2500350600
3000400600
4000500750
50007001250
60008001250