Chapter 9 Table 4 — Conduit Dimensions

Dimensions and Percent Area of Conduit and Tubing

Trade Size Nominal Internal Diameter Total Area
100%
60% 1 Wire
53%
2 Wires
31%
Over 2 Wires
40%
mm in. mm2 in.2 mm2 in.2 mm2 in.2 mm2 in.2 mm2 in.2
½15.30.6021840.2851100.171980.151570.088740.114
¾20.40.8043270.5081960.3051730.2691010.1571310.203
126.11.0295350.8323210.4992840.4411660.2582140.333
34.51.3609351.4535610.8724960.7702900.4503740.581
40.41.59012821.9867691.1926791.0533970.6165130.794
252.02.04721243.29112741.97511261.7446581.0208501.316
62.12.44530294.69518172.81716052.4889391.45512121.878
377.33.04246937.26828164.36124873.85214552.25318772.907
89.43.52162779.73737665.84233275.16119463.01825113.895
4101.53.998809112.55448557.53242886.65425083.89232365.022
5127.45.0161274819.761764911.857675610.47339526.12650997.904
6153.26.0311843328.5671106017.140976915.14157148.856737311.427

Not sure what size conduit you need? Check out the Conduit Size Calculator!

Back to all tables

DISCLAIMER: All tables on this site are based on the 2020 National Electric Code. The law under your local jurisdiction may be different than what is presented here. Check your local jurisdiction's laws before attempting to do electrical work.

Please report any discrepancies or feedback to feedback -AT- conduit -DOT - site