Chapter 9 Table 4 — Conduit Dimensions

Dimensions and Percent Area of Conduit and Tubing

Trade Size Nominal Internal Diameter Total Area
100%
60% 1 Wire
53%
2 Wires
31%
Over 2 Wires
40%
mm in. mm2 in.2 mm2 in.2 mm2 in.2 mm2 in.2 mm2 in.2
⅜12.50.4941230.192740.115650.102380.060490.077
½16.10.6322040.3141220.1881080.166630.097820.126
¾21.10.8303500.5412100.3251860.2871080.1681400.216
126.81.0545640.8733380.5242990.4631750.2712260.349
1¼35.41.3959841.5285900.9175220.8103050.4743940.611
1½40.31.58812761.9817661.1896761.0503960.6145100.792
251.62.03320913.24612551.94811081.7206481.0068361.298
2½63.32.49331474.88118882.92916682.5879761.51312591.952
378.43.08548277.47528964.48525583.96214962.31719312.990
3½89.43.52062779.73137665.83933275.15719463.01725113.892
4102.14.020818712.69249127.61543396.72725383.93532755.077

Not sure what size conduit you need? Check out the Conduit Size Calculator!

Back to all tables

DISCLAIMER: All tables on this site are based on the 2020 National Electric Code. The law under your local jurisdiction may be different than what is presented here. Check your local jurisdiction's laws before attempting to do electrical work.

Please report any discrepancies or feedback to feedback -AT- conduit -DOT - site