Chapter 9 Table 4 — Conduit Dimensions

Dimensions and Percent Area of Conduit and Tubing

Trade Size Nominal Internal Diameter Total Area
100%
60% 1 Wire
53%
2 Wires
31%
Over 2 Wires
40%
mm in. mm2 in.2 mm2 in.2 mm2 in.2 mm2 in.2 mm2 in.2
½15.80.6221960.3041180.1821040.161610.094780.122
¾20.90.8243430.5332060.3201820.2821060.1651370.213
126.61.0495560.8643340.5182950.4581720.2682220.346
35.11.3809681.4965810.8985130.7933000.4643870.598
40.91.61013142.0367881.2226961.0794070.6315260.814
252.52.06721653.35612992.01411471.7796711.0408661.342
69.42.73137835.85822703.51520053.10511731.81615132.343
385.23.35657018.84634215.30830224.68817672.74222803.538
97.43.834745111.54544716.92739496.11923103.57929804.618
4110.14.334952114.75357138.85250467.81929524.57338085.901

Not sure what size conduit you need? Check out the Conduit Size Calculator!

Back to all tables

DISCLAIMER: All tables on this site are based on the 2020 National Electric Code. The law under your local jurisdiction may be different than what is presented here. Check your local jurisdiction's laws before attempting to do electrical work.

Please report any discrepancies or feedback to feedback -AT- conduit -DOT - site